Quote:
Originally Posted by MIPS View Post
Well waddya know, the compressor still works.

I found a 57mfd 230v Mallory motor start cap and wondered what would happen if I swapped out the old 88mfd 165V. Sure enough once the cap was swapped out and power was applied the compressor puttered to life and spit out a little bit of oil.
Okay then, so aside from a bad condenser coil the refrigeration unit suddenly became a rebuild candidate. Now to ask around to see if I can steal a new coil off another unit with a burned out compressor.
I had a hunch that your compressor would be OK - given that one of the lines had a big hole in it, it probably lost its freon fast enough that the pressure switch prevented the compressor from being fried. Assuming the rupture occurred before it was abandoned of course.

Any luck finding a schematic for the wiring? Looks like you're almost ready to start putting the vending machine back together.
Reply With Quote